## apcupsd.conf v1.1 ## UPSCABLE smart UPSTYPE smartups DEVICE /dev/ttyS0 LOCKFILE /var/lock UPSCLASS standalone UPSMODE disable
Normally you would have many more configuration directives to completely customize your installation, but this example shows you the minimum required.
## apcupsd.conf v1.1 ## UPSCABLE smart UPSTYPE smartups DEVICE /dev/ttyS0 LOCKFILE /var/lock UPSCLASS netmaster UPSMODE net NETTIME 10 NETPORT 6666 SLAVE slave1.mynetwork.com SLAVE slave2.mynetwork.com
Note, the main difference from the stand alone configuration si that you have specified UPSCLASS netmaster and UPSMODE net. In addition, you have specified one or more slave machines.
## apcupsd.conf v1.1 ## UPSCABLE ether UPSTYPE smartups LOCKFILE /var/lock UPSCLASS netslave UPSMODE net NETPORT 6666 MASTER master.mynetwork.com
The main difference from the master configuration is that you have specified UPSCABLE ether and UPSCLASS netslave. In addition, you have specified a single controlling master.
In this configuration, the shutdown will be initiated by the master. It is also possible to specify BATTERYLEVEL, MINUTES, and TIMEOUT configuration directives in the Slave machine that will cause the slave to shutdown before the master. This can often be useful if the slave is less important than the master and you wish to reduce battery power consumption so that the master can remain up longer during a power outage.